Electrical Design

This section provides electrical design guidelines for Power Block 2000.

Electrical Supply Requirements

This section provides electrical supply requirements for Power Block 2000.

Transformer Configuration

The table below provides the transformer configuration:

Transformer Configuration
  Transformer Configuration
Parameter US Canada

Input rating

480 V AC, 3-phase,

1000 A, 60 Hz

600 V AC, 3-phase,

900 A, 60 Hz

Electrical service configuration

480 V AC 3-phase grounded WYE (Y) configuration

 

480 V AC 3-phase Delta (D) configuration (corner-grounded Delta transformer) is not acceptable

600 V AC 3-phase grounded WYE (Y) configuration

 

600 V AC 3-phase Delta (D) configuration (corner-grounded Delta transformer) is not acceptable

Product connection

Power Block 2000 must be connected to L1, L2, and L3 (neutral not required)

Power Block 2000 is available in two factory configurations: with a Neutral landing or without one. A Neutral connection is not required for standard charging applications. However, some Vehicle‑to‑Grid (V2G) systems rely on phase‑to‑neutral voltage measurements for control functions. When planning a V2G deployment, contact ChargePoint to ensure the correct Power Block 2000 configuration is selected.

Branch Circuits and Overcurrent Protection

Charging stations are considered continuous load devices (EVs draw maximum load for long durations). Therefore, electrical branch circuits to EVClosed Electric Vehicle chargers must be sized at 125% of the load on each leg of a 3‑phase panel for North American (NA) installations, in accordance with National Electric Code requirements.

When planning multiple EVClosed Electric Vehicle charging stations, it is best practice to segment non-continuous and continuous loads, with all branch circuits for EVClosed Electric Vehicle charging on a dedicated electrical panel assembly with adequate circuit breakers. When sizing new electrical panels dedicated for EVClosed Electric Vehicle charging, all branch circuits must support continuous load.

Power Block 2000 is available in multiple power ratings:

  • In the US: 200 kW, 400 kW, 600 kW

  • In Canada: 225 kW, 450 kW, 625 kW, 675 kW

Each Power Block 2000 requires its own circuit breaker. Recommended breaker sizing is given below. Check with local code for breaker size requirements.

IMPORTANT: The breaker sizes in the 100% Rated column apply only when using circuit breakers and associated equipment that are specifically listed and installed for 100% continuous operation. Standard circuit breakers are typically applied under the 80% continuous-load rule. Do not use the breaker sizes in the 100% Rated column unless the upstream overcurrent protection equipment is specifically rated and installed for 100% continuous loading. Consult applicable electrical codes and manufacturer documentation.

Recommended breaker sizing for the US region (480 V AC):

AC Circuit Breaker Size, U.S.

Max. Output Power

Max. Input Current

Recommended 100% Rated Breaker

Recommended 80% Rated Breaker

200 kW

258 A

300 A

350 A

400 kW

515 A

600 A

700 A

600 kW

769 A

800 A

1000 A

Recommended breaker sizing for the Canada region (600 V AC):

AC Circuit Breaker Size, Canada

Max. Output Power

Max. Input Current

Recommended 100% Rated Breaker

Recommended 80% Rated Breaker

225 kW

232 A

250 A

300 A

450 kW

463 A

500 A

600 A

625 kW

641 A 700 A 850 A
675 kW

691 A

700 A

900 A

  • For upstream breakers ≥ 1000 A, provide GFPE in accordance with NECClosed National Electric Code and CEC (typically implemented via LSIG breakers).

  • For breakers < 1000 A, GFPE is generally not required; LSI or thermal-magnetic breakers may be used subject to coordination requirements.
  • Power Block 2000 has a short circuit current rating of 100 kA.

Power Block 2000 is tested to IEC 61000-4-5, Level 5 (6 kV @ 3000 A) standards.

Disconnect and Emergency Shutoff

ChargePoint recommends installing a local AC disconnect switch, separate from the shunt trip wiring, between each cabinet and the electrical panel. A local disconnect is especially important when the main electrical panel or utility room is distant, not within line of sight, or has restricted access.

Power Block 2000 can be ordered with an optional AC disconnect switch. When included, the switch is located on the intake side of the cabinet.

Consult local electrical codes to determine disconnect and emergency shutoff requirements. Recent and upcoming code cycles include significant updates to disconnect and emergency shutoff requirements. Always verify compliance with the latest adopted electrical code.

Shunt Trip Wiring (optional)

Each cabinet of Power Block 2000 provides a set of unpowered (dry) contacts to connect to an optional shunt trip device. These contacts are rated to 240 VAC and 6 amps.

Wiring sections to and from Power Block 2000 are deactivated when unsafe conditions are detected, such as unintended cover panel removal. A breaker reset is required any time the shunt trip is activated.

If installed, each cabinet of the Power Block 2000 must be wired to the shunt trip unit of its own upstream circuit breaker. Upstream AC power must be shut off at the panel to remove shock risk inside the Power Block 2000. All shunt trip behavior is already hard-coded into the Power Block 2000 and has no programmable variables.

Emergency stop devices are governed by local and regional codes and may be required in some sites. If one is required by code or by the site, confirm specifications with your ChargePoint representative.

Shunt Trip Wiring Diagram

  1. Electrical panel

  2. Power Block 2000

  3. Control voltage supply, maximum 240 VAC

  4. Shunt trip circuit breaker

  5. Shunt trip coil

  6. Auxiliary contacts (closed when main contacts are closed)

  7. 3-phase AC main

  8. Power Block 2000 shunt trip contacts, Normally Open (inside the auxiliary power supply, accessible on field wiring terminal block)

  9. 3-phase Power Block 2000 AC input

Grounding Requirements

Power Block 2000 must be connected to a grounded, metal, permanent wiring system. Ensure a grounding conductor that complies with local codes is properly grounded to earth at the service equipment or, when supplied by a separate system, at the supply transformer.

When connecting Power Block 2000 to Power Links, charging components must be ground bonded in sequence from Power Block 2000 to Power Link.

Check local code to ensure compliance to grounding requirements. Some regions also require a grounding rod to be installed adjacent to each component.

The leakage current from Power Block 2000 to the protective earth conductor can reach up to 200 mA.

Soft Shutdown

The soft shutdown function is an optional feature that can be installed as a way to stop a charge session on a Power Block 2000. It is not meant to safely service the Power Block 2000 or take the place of a AC disconnect switch.

Each cabinet of a Power Block 2000 supports connection to a soft shutdown switch.

To use this feature, the installer must select and mount a physical soft shutdown switch (one per Power Block 2000 cabinet) with the following specifications:

When creating the site drawings, consider where any soft shutdown switches should be positioned. If applicable, consider disability and accessibility regulations for your region when choosing switch locations.

Soft shutdown switch requires a dedicated wire conduit. For more information, refer to Conduit Requirements.

When the switch is closed, the Power Block 2000 software ends the current charging session with a normal stop, then opens DC contactors in the Power Block 2000 cabinet. The station stays in this state regardless of station power, not allowing operation. Only a service technician can place the Power Block 2000 cabinet back into service after the switch is reset to Open.

WARNING: The external DC output wires from the Power Block 2000 could still be energized with the switch closed.

Safety Hub

Safety Hub is a Power Block 2000 feature that provides continuous electrical-isolation monitoring to enhance system safety. When required, Safety Hub uses a dedicated twisted-pair connection routed from the Power Block 2000 Safety Hub Board to each associated Power Link. These conductors may share the same conduit as the 48 V DC and Ethernet wires serving the Power Links.

Safety Hub wiring requirements vary by Power Link model. Depending on the specific Power Link used in the installation, one of the following configurations will apply:

  • Some Power Link models require a direct Safety Hub twisted-pair connection between the Power Block 2000 Safety Hub Board and the Power Link.

  • Other Power Link models do not require a Safety Hub wire connection. For these models, a jumper wire must be installed on the Power Block 2000 Safety Hub Board instead of running twisted-pair wiring to the Power Link. This jumper is supplied with the Power Link and does not need to be sourced separately. Installation details are provided in the Express Distro Power Block 2000 Installation Guide.

Refer to the site design guide and installation guide of the Power Link model specific to your project to determine whether Safety Hub twisted wire connection is required.

Wiring and Conduit Requirements

Refer to the Express Distro Power Block 2000 Datasheet at ChargePoint Product Reference Documentation for full product specifications. Using that data, ensure that the installation location is equipped with service wiring that support the station's power requirements.

Conduit and wire size are determined based on current. Service wiring in conduit or armored cable must be run as required to comply with local electrical codes. Consult national and local codes or a project engineer to determine the grade, quality, and size of the conduit or cable.

  • All wiring and conduit is supplied by the contractor unless otherwise indicated.

  • For V2G and energy storage applications, contact ChargePoint for wire and conduit requirements.

Wire Run Lengths

Wire run length guidelines are given below:

  • The maximum total external DC output wire run length from a Power Block 2000 to a connected Power Link 2000 must not exceed 200 m (656 ft). Refer to the cluster configuration provided by ChargePoint for interconnect details.

  • 48 V DC wire and Ethernet run length between Power Block 2000 and a Power Link must not exceed 200 m (656 ft).

  • At minimum, there must be one 48 V DC wire pair connecting from the Power Block 2000 to each Power Link. If the distance between the Power Block 2000 and a Power Link exceeds 100 m (328 ft), contact ChargePoint to determine if an additional 48 V DC wire pair must be run to compensate for voltage drop.

Ethernet Cable Type and Configuration

Specifications for Ethernet cable type and configuration are given below:

  • For Ethernet communications between any two nodes (for example, between a Power Block 2000 and a Power Link):

    • For distances up to 100 m (328 ft): use outdoor-rated Cat6 Shielded Twisted Pair (STPClosed Shielded Twisted Pair) cable. Lesser grades of cable do not provide the required noise immunity.

    • For distances between 100 m (328 ft) and 200 m (656 ft): use the Paige OSP Shielded GameChanger cable (see paigedatacom.com/gamechanger) or other extended-reach cable rated for 200 m (328 ft).

  • An Ethernet cable run between a Power Block 2000 and a Power Link must have the shield terminated only at the Power Block 2000 end, not at the Power Link end.

Conduit Requirements

In regions that use conduits, wire conduits may enter Power Block 2000 through a Concrete Mount Template (CMT) or through a skid via conduit stub-ups. In regions that do not use conduits and/or use armored cables, the cables may be laid per the conduit layout defined by the CMT.

If using conduits:

  • Conduits must be sealed to maintain a Pollution Degree 2 environment.

  • Conduits must not have bell ends. Conduits with bell ends may interfere with tolerances inside the Power Block 2000.

  • If using conduit stub-ups (ie., not using surface conduit entry), conduits must stub-up 13–25 mm (0.5–1 in) above the mounting surface.

Below is a sample depiction of wire entry via conduit stub-ups.

IMPORTANT: Conduit and wire size and quantity are shown for illustrative purposes only. The actual quantity and size of conduits and wires for your specific site may vary and shall depend on site specific requirements.

Exterior Parts

Ref

4 DC Output

8 DC Output

(1)

Cabinet front side

(2)

Cabinet intake (right) side

(3)

48 V DC, Ethernet, and Safety Hub

(4)

AC input

(5)

Shunt trip

(6)

EXT A

EXT A

(7)

EXT B

(8)

EXT B

EXT C

(9)

EXT D

(10)

EXT C

EXT E

(11)

EXT F

(12)

EXT D

EXT G

(13)

EXT H

IMPORTANT: The following table provides the maximum size and quantity of conduits that can be installed on Power Block 2000 configured for standard wire entry. The actual conduit size and quantity must be chosen based on site specific wiring requirements.

Power Block Stub-up Conduit Specifications

Conduits For

Conduit Quantity x Trade Size

AC input

3 x 4 inch max.

or

4 x 2.5 inch max.

Exernal DC output

(E.g. EXT A, EXT B, EXT C, EXT D)

1 x 4 inch max. per output

or

2 x 3 inch max. per output

48 V DC, Ethernet, and Safety Hub (*)

1 x 1 inch to each Power Link

1 inch size conduit is required. The quantity of conduits will depend on the configuration.

Optional Features

(Soft shutdown switch and shunt trip)

1 x 3/4 inch max. per feature

(*) 48 V DC, Ethernet, and Safety Hub wires travel in the same conduit when connecting Power Block 2000 to a Power Link. Safety Hub wires are required for only for certain models of Power Link. Refer to the site design guide and installation guide of the Power Link model specific to your project to determine whether Safety Hub twisted wire connection is required.

Wire Terminal and Bus Bar Locations

This section illustrates terminal and bus bar locations for the Power Block 2000 in a 4 DC output configuration. Illustrations for 8 DC output and 12 DC output configurations will be provided in a future revision.

The following identifies the wire ports, terminals, and bus bars accessible from the intake side (right side) of each Power Block 2000 cabinet. (Safety shields are hidden from view.)

Express Foundation and Cables Entry

Ref

Part

(1)

Safety Hub ports

(2)

Ethernet ports

(3)

Terminal block for 48 V DC and soft shutdown switch wires

(4)

Shunt trip terminals

(5)

EXT A bus bars

(6)

EXT B bus bars

The following identifies the wire ports, terminals, and bus bars accessible from the exhaust side (left side) of each Power Block 2000 cabinet (Safety shields are hidden from view).

Express Foundation and Cables Entry

Ref

Part

(1)

Ground/PE bar (with wire landing studs)

(2)

EXT D bus bars

(3)

EXT C bus bars

(4)

AC input (L1, L2, L3) and neutral bus bars

AC input and external DC output conductors must extend a minimum height of 600 mm (24 in) from the finished mounting surface to ensure they reach their landings.

Wire Specifications

The requirements and specifications in this section reflect what is supported by Power Block 2000. When Power Block 2000 is connected to another ChargePoint product, such as a Power Link charging dispenser or battery, conductor characteristics may be further constrained by the connected product. Refer to the site design guide for each connected product and follow the most stringent requirements.

The following table summarizes the conductor requirements for each circuit.

Conductor Requirements

Circuit / Application

Min. Conductor Voltage Rating

Number of Poles

Insulation

Type

Conductor Material / Min. Temperature Rating

AC Input

600 V AC

3 + PE

 

 

 

 

 

Must be THHNClosed Thermoplastic High Heat-Resistant Nylon-Coated/THHWClosed Thermoplastic High Heat-Tesistant, Water-Resistant/THWClosed Thermoplastic Heat-Resistant, Water-Resistant-2/THWN-2, based on the installation environment (e.g., dry, damp or wet conditions)

Must be copper or aluminum, rated for 90°C (194°F)

 

 

 

 

 

External DC Output

1000 V

2 + PE

Must be XHHW / XHHW‑2, based on the installation environment (e.g., dry, damp or wet conditions)

Must be copper or aluminum, rated for 90°C (194°F)

48 V DC Output

300 V

2

Select type to be suitable for the installation environment (e.g., dry, damp or wet conditions)

 

 

Copper wire only

 

 

Shunt Trip

Same voltage rating as AC input conductors (due to routing proximity to power conductors)

Twisted pair

Safety Hub

300 V

Twisted pair

IMPORTANT: Following are wire design specifications for Power Block 2000, including the maximum quantity and size that the wire terminals can accommodate. All sizing assumes a maximum ambient temperature of 50 °C (122 °F). Where the maximum wire size is listed, the actual wire quantity and size must be chosen based on site-specific wiring requirements and in accordance with the maximum allowed conduit filling rate per local code.

Wire Specifications

Wire

Max. Current

Quantity

Size

AC input (US)

200 kW unit: 258 A

400 kW unit: 515 A

600 kW unit: 769 A

Max. 18 wires

(six per phase)

Max. 300 MCM

AC input (Canada)

225 kW unit: 232 A

450 kW unit: 463 A

625 kW unit: 641 A

675 kW unit: 691 A

AC ground (PE)

-

Max. 3 wires

(1 per AC conduit)

Refer to local code for size

External DC outputs

(E.g., EXT A, EXT B, EXT C, EXT D)

250-600 A, depending on Power Link model and configuration

Max. 8 wires per output

(four per pole)

Max. 300 MCM (*)

DC grounding

-

Max. 2 wires per DC output

(1 per output conduit)

Refer to local code for size

48 V DC output

32 A

Max 4 wires per connected Power Link

(2 wire pairs; each pair has one wire per pole) (**)

6 AWGClosed American Wire Gauge

Ethernet

-

1 per connected Power Link

1 for hardwire Ethernet (if needed)

Outdoor-rated Cat6 STPClosed Shielded Twisted Pair or Paige OSP Shielded GameChanger (***)

Safety Hub

-

2 wires per connected Power Link (****)

14 AWGClosed American Wire Gauge

Soft shutdown switch

-

2 wires

14 AWGClosed American Wire Gauge

Shunt trip

6A

2 wires

14 AWGClosed American Wire Gauge

(*) If Aluminum AA8000 conductors are used, max. 400 MCM can be accommodated. (**) The required number of 48 V DC wire pairs depends on the distance between Power Block 2000 and Power Link. See Wire Run Lengths. (***) The required Ethernet cable type depends upon the cable run length. See Ethernet Requirements. (***) The required Ethernet cable type depends upon the cable run length. See Ethernet Requirements. (****) Safety Hub is required only for certain models of Power Link. Refer to the installation guide of the Power Link model specific to your project to determine if Safety Hub twisted wire connection is required.

For AC input, Power Block 2000 allows a maximum of 18 total current carrying conductors. If utilizing this wiring configuration, install spreader bars at the breaker or transformer to split the outputs across the high number of conductors.

After pulling conductors through conduit, all AC input and external DC output conductors must undergo insulation resistance testing to verify that insulation has not been damaged during the pull.

Plan for lugs and terminations using the following information:

  • Use copper lugs for copper conductors and aluminum lugs for aluminum conductors. The lugs must be nickel-, tin-, or silver-plated compression lugs (not mechanical lugs). Nickel-plated lugs installed with dielectric grease are recommended.

  • When using aluminum lugs, ChargePoint recommends applying an appropriate antioxidant compound to aluminum conductors when terminating into tin-, nickel-, or silver-plated lugs, where required by code or specified by the lug manufacturer.

Lug Specifications

Wire

Termination

AC input

Lug: Compression lug; short barrel and tongue with single hole sized for M12 (0.5 in) stud

Max. tongue width: 36 mm (1.3 in).

AC PE/ground

Lug: Short barrel and tongue with single hole sized for M6 (0.25 in) stud

External DC output

Lug: Compression lug; short barrel and tongue with single hole sized for M12 (0.5 in) stud.

Max. tongue width: 36 mm (1.3 in).

DC grounding

Lug: Short barrel and tongue with single hole sized for M6 (0.25 in) stud.

48 V DC output

Stripped wire end or ferrule

Ethernet

RJ45 connector, shielded

Safety Hub

Stripped wire end

Soft shutdown switch

Stripped wire end or ferrule

Shunt trip

Stripped wire end or ferrule