Appendix A: Surface Conduit Entry Kit Installation

The Surface Conduit Entry (SCEClosed Surface Conduit Entry) kit can be used at sites where the wires cannot be laid underground or when the site is not using stub-up entry through Concrete Mounting Template (CMT) embedded in a concrete pad.

This SCEClosed Surface Conduit Entry kit is only for the pedestal-mount variant of Power Link 2000.

Required Tools and Materials

In addition to the tools and materials required for installing Power Link 2000, the installer must bring the following tools and materials for the installation of SCEClosed Surface Conduit Entry kit.

Tools

Orange and white icon that represents a tool or action.

Power drill (with level feature recommended)

Orange and white icon that represents a tool or action.

Sheet metal hole saw with pilot drill bit for conduit sizes listed on site drawings

Orange and white icon that represents a tool or action.

Concrete drill bits

  • 20 mm (13/16 in) or per epoxy manufacturer's recommendation for M16 (5/8 in) anchor bolts

  • 6 mm (1/4 in) to drill pilot hole

 

Orange and white icon that represents a tool or action.

24 mm hex socket or open ended wrench

Orange and white icon that represents a tool or action.

750 ml of epoxy with bonding strength of 11.7 MPa minimum, compressive strength of 82.7 MPa minimum, and tensile strength of 49.3 MPa minimum, such as Hilti HIT-RE 500 V3 (normal cure time), Hilti HIT-HY 200-A (fast curing), or similar.

Different epoxy types have different cure times at various temperatures. Check local temperatures for the site in advance to help choose an appropriate epoxy.

Materials

  • Refer to the site drawings for the actual quantity and size of conduits required for the site.

  • Use LB conduit bodies to route wires into Power Link 2000 from rear left or rear right.

  • Use suitable conduit fittings to secure and seal the conduits and/or conduit bodies.

Following are the maximum quantity and size of conduits that can be installed on Power Link 2000 using the SCEClosed Surface Conduit Entry kit:

Conduit Specifications
Conduits For Conduit Quantity x Trade Size
 

North America

Europe

HV DCClosed High Voltage Direct Current wires

 

2 x 3 inch max.

2 x 78 mm max.

LVClosed Low Voltage DC input wires and Ethernet cable

2 x 1 inch (*)

2 x 27 mm (**)

Optional features

(Ethernet to USBClosed Universal Serial Bus or soft shutdown switch)

2 x 3/4 inch max.

2 x 21 mm max.



(*) In North America, 1 inch size conduit is required for LV DCClosed Low Voltage Direct Current input wires and Ethernet cables. The quantity of conduit will depend on the configuration.



(**) In Europe, 27 mm size conduit is required for LV DCClosed Low Voltage Direct Current input wires and Ethernet cables. The quantity of conduit will depend on the configuration.

Kit Components

SCE Kit For LCC Power Link 2000

Check the package for the following components:

For any missing component, contact ChargePoint support at chargepoint.com/support.

Labeled diagram of product, tools or parts.

(a) Templates for marking and drilling conduit holes.

(b) Surface mount template for marking and drilling holes into concrete surface.

(c) Rear lower cover replacement for SCEClosed Surface Conduit Entry.

(d) M16 anchor bolts (x4) for mounting Power Link 2000.

(e) Mounting bracket for conduits.

(f) Hardware bag, which contains the following components:

  • M16 nuts, washers, and protective caps for anchor bolts (d).

  • M5 nuts (x4) for mounting bracket (e).

  • M5 screws (x2) for gland plate (g).

(g) Gland plate for closing the conduit opening.

The SCEClosed Surface Conduit Entry kit for LCCClosed Liquid Cooled Cable also contains the nameplate plate to affix to the SCEClosed Surface Conduit Entry rear lower cover (c).

SCE Kit For non-LCC Power Link 2000

Check the package for the following components:

For any missing component, contact ChargePoint support at chargepoint.com/support.

Labeled diagram of product, tools or parts.

  1. Template for marking and drilling conduit holes.

  2. M16 anchor bolts and nuts with protective caps (x4) for mounting Power Link 2000.

  3. Surface mount template for marking and drilling holes into concrete surface.

  4. Gland plate for closing the conduit opening.

  5. M5 screws (x2) to install gland plate.

Install Anchor Bolts

To install anchor bolts, complete the following steps:

  1. Refer to the site drawings and place surface mount template at the proposed location.

    Make sure to leave enough clearance at the rear side (610 mm or 2 ft) for surface conduit entry and servicing.

  2. Use a marker to mark the locations for the anchor bolts and remove the surface mount template.

    Technical illustration depicts the procedural step.

  3. Use the 6 mm (0.25 in) concrete drill bit to drill a pilot hole about 51 mm (2 in) deep at each marked location. The holes must be parallel to each other and perpendicular to the surface.

  4. Use the 25 mm (1 in) concrete drill bit to drill an anchor hole a minimum of 229 mm (9 in) deep. Anchor bolts must have 76 mm +/- 12.7 mm (3 in +/- 0.5 in) above surface.

    Technical illustration depicts the procedural step.

  5. Use a vacuum to clean the concrete residue.

    Technical illustration depicts the procedural step.

  6. Place surface mount template on the surface again. Verify that the anchor holes align with the holes in the surface mount template.

  7. Prepare the epoxy. Ensure the applicator is dispensing correctly mixed epoxy before beginning work (for example, the Hilti epoxy is white when unmixed and gray when mixed).

  8. Fill the first anchor hole with epoxy until the epoxy is about 44.5 mm (1.75 in) from the top of the hole.

    Continue immediately to the next step because the epoxy sets within about eight minutes.

    Technical illustration depicts the procedural step.

  9. Insert anchor bolt into the hole. Rotate the anchor bolt as you insert it to draw epoxy into the threads. If needed, add more epoxy until it fills hole to surface level. Use paper towels to wipe off any excess.

    Technical illustration depicts the procedural step.

  10. Use a level to check that the anchor bolt is plumb. If needed, adjust it while the epoxy is still setting.

    Technical illustration depicts the procedural step.

  11. Measure the bolt exposed above the surface and it must be 76 mm (3 in).

    Technical illustration depicts the procedural step.

  12. Repeat the above epoxy steps for each of the other three anchor bolts.

  13. If product station will not be immediately installed, insert protective caps over the anchor bolts.

    Technical illustration depicts the procedural step.

  14. Allow the epoxy to cure for the initial cure time listed on the epoxy usage instructions before beginning to install Power Link 2000.

  1. Install Power Link 2000 onto the anchor bolts (see Install Power Link 2000 ).

Install Gland Plate

To install gland plate, complete the following steps:

Install gland plate to seal the conduit opening in Power Link 2000's bottom and prevent rodent ingress. If the SCE kit you received doesn't have a gland plate, apply the duct seal compound supplied in the Power Link 2000 package to fill the conduit opening. Make sure that it is fully sealed.
  1. Find the M5 screws (x2) shipped in the SCE kit package.

  2. Remove screws (x2) to remove the conduit sleeve.

    Technical illustration depicts the procedural step.

  3. Install the gland plate using the M5 screws (x2) and torque the screws to 4.5 Nm (40 in-lb).

    Technical illustration depicts the procedural step.

 

Install Surface Conduits (LCC)

Skip this entire procedure for non-LCCClosed Liquid Cooled Cable variant of Power Link 2000.

Before you Begin

Refer to the site drawings and determine from which side of the Power Link 2000 the wires must enter from.
  1. If not already removed, remove the following:

    1. Cable cap

    2. Side panels

    3. Rear upper cover

    4. Loosen screws (x6) to remove the rear lower cover.

      Technical illustration depicts the procedural step.

  2. Open lower enclosure door.

  3. Install gland plate.

Install Conduits

To install conduits, complete the following steps:

  1. Align and hold templates against the lower enclosure wall.

    Technical illustration depicts the procedural step.

  2. Mark pilot hole locations on the lower enclosure wall and remove the templates.

    • If wires need to enter from rear left or right side of the Power Link 2000, mark LVClosed Low Voltage holes on the upper template.

      Technical illustration depicts the procedural step.

    • If the wires need to enter the rear of the Power Link 2000 from straight on or from above the entry point, mark LVClosed Low Voltage holes on the lower template.

      Technical illustration depicts the procedural step.

  3. Using a suitable hole saw, position the hole saw's pilot drill bit on the marked location, and cut a hole into the lower enclosure wall. Repeat for other marked locations.

    To cut holes to correct size, refer to the site drawings for the actual conduit dimensions. For the maximum conduit size supported by the Power Link 2000, refer to the Express Plus Power Link 2000 Site Design Guide, available at ChargePoint Product Reference Documentation.

    The illustrations shown below are for demonstration purposes only. Make sure to cut holes at suitable locations per wire routing proposed in the site drawings.

    Technical illustration depicts the procedural step.

  4. Cut corresponding conduit entry locations on the mounting bracket.

    Technical illustration depicts the procedural step.

  5. Vacuum all metal shavings.

    Technical illustration depicts the procedural step.

  6. Align and install mounting bracket on the back of Power Link 2000. Torque the nuts (x4) to 4.5 Nm (40 in-lb).

  7. Install the new SCEClosed Surface Conduit Entry rear lower cover.

    1. Align and seat cover onto the alignment pins (x2) on the frame.

      Technical illustration depicts the procedural step.

    2. Torque the screws (x6) to 4.5 Nm (40 in-lb).

      Technical illustration depicts the procedural step.

  8. Install LB type conduit bodies and/or conduits into the holes.

    Leave 25 mm (1 in) of clearance between the conduit bodies and the SCEClosed Surface Conduit Entry rear lower cover so that the cover can be removed for service without impacting the conduit bodies.

    Technical illustration depicts the procedural step.

  9. Install the remaining components, such as DC input wires, charging cables, cable management kit (CMKClosed Cable Management Kit), and covers, and complete the installation.

Install Surface Conduits (Non-LCC)

Skip this entire procedure for LCCClosed Liquid Cooled Cable variant of Power Link 2000.

Refer to the site drawings and determine from which side of the Power Link 2000 the wires must enter from.
  1. Open the lower enclosure door.

  2. Install the gland plate.

  3. Align and hold template against the rear lower cover.

    Technical illustration depicts the procedural step.

  4. Mark pilot hole locations on the rear lower cover and remove the template.

    Technical illustration depicts the procedural step.

  5. Using a suitable hole saw, position the hole saw's pilot drill bit on the marked location, and cut a hole into the rear lower cover. Repeat for other marked locations.

    To cut holes to correct size, refer to the site drawings for the actual conduit dimensions. For the maximum conduit size supported by the Power Link 2000, refer to the Express Plus Power Link 2000 Site Design Guide, available at ChargePoint Product Reference Documentation.

    Technical illustration depicts the procedural step.

  6. Vacuum all metal shavings.

    Technical illustration depicts the procedural step.

  7. Install LB type conduit bodies and/or conduits into the holes.

    Technical illustration depicts the procedural step.

  8. Install the remaining components, such as DC input wires, charging cables, cable management kit (CMKClosed Cable Management Kit), and covers, and complete the installation .