Wire the Charging Station

Read the following details carefully before wiring the AC terminals.

AC Terminal Labels and Meanings
Label Meaning

N

Neutral (single phase or three phase grid connection)

L1

Line 1 (single phase or three phase grid connection)

L2

Line 2 (only for three phase connection, leave unconnected if single phase)

L3

Line 3 (only for three phase connection, leave unconnected if single phase)

PE/GNDClosed Ground

Protective Earth/Ground (single phase or three phase grid connection)

Acceptable wire sizes are 2.5 - 16 mm2. Consult with local wiring guides for maximum current (measured in amps) of the cable.

Torque Guidelines

Follow these guidelines when torquing wires.

Torque Values for AC Wiring
Wire size Torque value

2.5 mm2

2.26 Nm (20 in-lb)

4 mm2

2.26 Nm (20 in-lb)

6 mm2

2.82 Nm (25 in-lb)

10 mm2

4.0 Nm (35 in-lb)

16 mm2

4.0 Nm (35 in-lb)

Connect AC Terminal Input Wires

Complete the following steps to connect AC terminal input wires:

  1. Wrap the PE/GNDClosed Ground wire around the wire guide and insert it into the PE/GNDClosed Ground terminal.

    Set the T20 torque value to one that is suitable for the wire being used, then tighten the screw on the PE/GNDClosed Ground terminal to the torque limit. (See Torque Guidelines for more information.)

    Technical illustration depicts the procedural step.

  2. Wrap the N, L3, L2, and L1 wires around the wire guide and insert each wire into the terminal block.

    Set the T20 torque value to one that is suitable for the wire being used, then tighten the screw on each of the four incoming wire terminals to the torque limit. (See Torque Guidelines for more information.)

    Technical illustration depicts the procedural step.

  3. Ensure all of the wires are tucked underneath the wire guide.

    Technical illustration depicts the procedural step.

  4. Adjust the current rating.

    ChargePoint Flex Plus charging stations must be connected to a dedicated circuit breaker.

    Use a T20 screwdriver to adjust the current dial (a).

    When configuring the station using the Installer app, the breaker value selected by the dial will be displayed in the app for reference. However, this value is read‑only and cannot be adjusted through the app.

    Labeled diagram of product, tools or parts.

    The charging station will be limited to this maximum current per phase, regardless of the charging station configuration.

    Current Dial Values

    Position

    Amperage

    Recommended Upstream Breaker

    32 A

    32 A (set in factory)

    40 A

    25 A

    25 A

    32 A

    20 A

    20 A

    25 A

    16 A

    16 A

    20 A

    12 A

    12 A

    16 A

    8 A

    8 A

    10 A

    X

    Reserved, defaults to 8 A

    10 A

    Y

    Reserved, defaults to 8 A

    10 A

    Z

    Reserved, defaults to 8 A

    10 A
For three-phase installations, use a three-phase MCBClosed Miniature Circuit Breaker rated according to the specified amperage and recommended upstream breaker requirements.

The following table lists some examples of recommended protection devices. Select a device that matches your configuration. Always ensure compliance with local electrical regulations:

Protection Device Type

Description

Country

Eaton Type Designation

1-phase breaker 3.7 kW

--

UK

--

3-phase breaker 11 kW

20 A breaker for the three-phase 16 A charging current

PLSM-C20/3N-MW

1-phase breaker 7.4 kW

-- --

3-phase breaker 22 kW

40 A breaker for the three-phase 32 A charging current

PLSM-C40/3N-MW

1-phase RCCBClosed Residual Current Circuit Breaker

RCDClosed Residual Current Device type A for the three-phase 16 A charging current

PFIM-25/4/003-A-MW

3-phase RCCBClosed Residual Current Circuit Breaker

RCDClosed Residual Current Device type A for the three-phase 32 A charging current

PFIM-40/4/003-A-MW

3-phase RCBOClosed Residual Current Breaker with Overload Protection

20 A RCBOClosed Residual Current Breaker with Overload Protection (MCBClosed Miniature Circuit Breaker+RCDClosed Residual Current Device Type A) for the three-phase 16 A charging current

MRB4-20/3N/C/003-A

 

Protection Device Type

Description

Country

Eaton Type Designation

1-phase breaker 3.7 kW

1-fase installatieautomaat van 20 A voor een laadstroom van 16 A

Netherlands

PLN6-C20/1N-MW

3-phase breaker 11 kW

3-fasen installatieautomaat van 20 A voor een laadstroom van 16 A

PLS6-C20/3N-MW

1-phase breaker 7.4 kW

1-fase installatieautomaat van 40 A voor een laadstroom van 32 A

PLN6-C40/1N-MW

3-phase breaker 22 kW

3-fasen installatieautomaat van 40 A voor een laadstroom van 32 A

PLS6-C40/3N-MW

1-phase RCCBClosed Residual Current Circuit Breaker up to 7.4 kW

1-fase type A aardlekschakelaar voor een laadstroom van 16 of 32 A

PFIM-40/2/003-A-MW

3-phase RCCBClosed Residual Current Circuit Breaker up to 22 kW

3-fasen type A aardlekschakelaar voor een laadstroom van 16 of 32 A

PFIM-40/4/003-A-MW

3-phase RCBOClosed Residual Current Breaker with Overload Protection

20 A RCBOClosed Residual Current Breaker with Overload Protection (MCBClosed Miniature Circuit Breaker+RCDClosed Residual Current Device type A) voor de 3-fasen laadstroom van 16 A

MRB4-20/3N/C/003-A

 

Protection Device Type

Description

Country

Eaton Type Designation

1-phase breaker 3.7 kW

1-fase installatieautomaat van 20 A voor een laadstroom van 16 A

Belgium

PLS4-C20/2-MW

3-phase breaker 11 kW

3-fasen installatieautomaat van 20 A voor een laadstroom van 16 A

PLS4-C20/4-MW

1-phase breaker 7.4 kW

1-fase installatieautomaat van 40 A voor een laadstroom van 32 A

PLS4-C40/2-MW

3-phase breaker 22 kW

3-fasen installatieautomaat van 40 A voor een laadstroom van 32 A

PLS4-C40/4-MW

1-phase RCCBClosed Residual Current Circuit Breaker up to 7.4 kW

1-fase type A aardlekschakelaar voor een laadstroom van 16 of 32 A

PFIM-40/2/003-A-MW

3-phase RCCBClosed Residual Current Circuit Breaker up to 22 kW

3-fasen type A aardlekschakelaar voor een laadstroom van 16 of 32 A

PFIM-40/4/003-A-MW

3-phase RCBOClosed Residual Current Breaker with Overload Protection

20 A RCBOClosed Residual Current Breaker with Overload Protection (MCBClosed Miniature Circuit Breaker+RCDClosed Residual Current Device type A) voor de 3-fasen laadstroom van 16 A

MRB4-20/3N/C/003-A

 

Protection Device Type

Description

Country

Eaton Type Designation

1-phase breaker 3.7 kW

--

France

--

3-phase breaker 11 kW

Disjoncteur de 20 A pour courant de charge triphasé de 16 A

PLSM-C20/3N-MW

1-phase breaker 7.4 kW

-- --

3-phase breaker 22 kW

Disjoncteur de 40 A pour courant de charge triphasé de 32 A

PLSM-C40/3N-MW

3-phase RCCBClosed Residual Current Circuit Breaker for 11 kW

Interrupteur différentiel de type A pour le courant de charge triphasé de 16 A

PFIM-25/4/003-A-MW

3-phase RCCBClosed Residual Current Circuit Breaker for 22 kW

Interrupteur différentiel de type A pour le courant de charge triphasé de 32 A

PFIM-40/4/003-A-MW

3-phase RCBOClosed Residual Current Breaker with Overload Protection

Disjoncteur différentiel 20 A (disjoncteur modulaire + interrupteur différentiel de type A) pour le courant de charge triphasé de 16 A

MRB4-20/3N/C/003-A

 

Protection Device Type

Description

Country

Eaton Type Designation

1-phase breaker 3.7 kW

--

Germany / Austria / Switzerland

--

3-phase breaker 11 kW

20-A-Leistungsschalter für den dreiphasigen 16-A-Ladestrom

PLSM-C20/3N-MW

1-phase breaker 7.4 kW

-- --

3-phase breaker 22 kW

40-A-Leistungsschalter für den dreiphasigen 32-A-Ladestrom

PLSM-C40/3N-MW

3-phase RCCBClosed Residual Current Circuit Breaker for 11 kW

Typ-A-FI-Schalter für dreiphasigen 16-A-Ladestrom

PFIM-25/4/003-A-MW

3-phase RCCBClosed Residual Current Circuit Breaker for 22 kW

Typ-A-FI-Schalter für dreiphasigen 32-A-Ladestrom

PFIM-40/4/003-A-MW

3-phase RCBOClosed Residual Current Breaker with Overload Protection

20 A FI/LS-Schalter (FI+LS Typ A) für dreiphasigen 16-A-Ladestrom

MRB4-20/3N/C/003-A

 

If you choose to use a wired Ethernet connection to connect the charging station to your home, connect the RJ45 connector to the station. Configure the details in the ChargePoint Installer app.

If Ethernet is being used to connect to a smart meter, refer to the Ethernet section for more details.

Close the Backplate

Complete the following steps to close the backplate:

  1. Ensure that the connections are secure.

  2. Make sure the current dial has been set correctly.

  3. Using a T20 screwdriver tighten all five screws to attach the backplate cover.

    Technical illustration depicts the procedural step.

  4. Torque each of the five screws to 0.5 Nm (4.5 in-lb).