Check Voltages
The following table lists the expected input voltage measurements.
|
Measure Between |
VAC (Plus or Minus 10%) |
|---|---|
|
L1R – L2/N R |
208/240 |
|
L1L – L2/N L |
208/240 |
|
L1R – GND |
120 |
|
L2R – GND |
120 |
|
L1L – GND |
120 |
|
L2L – GND |
120 |
-
Turn power ON at the circuit breaker panel.
-
Using a solenoid type voltmeter, check that the voltages at the charging station’s terminal block are as listed in the table above.
-
Insert the meter probes into the holes at the top of each terminal block and check the input voltage.
-
If the voltages are not within 10% of the voltages in the table above, ensure the wiring has been properly connected. Refer to the detailed wiring diagrams in this section.
-
For grounding requirements, see the CP6000 Datasheet on ChargePoint Product Reference Documentation.
-
-
Resolve any wiring issues and ensure voltages are correct.
-
Turn power OFF at the circuit breaker panel.